RAIN PLUS 2
Direct starting electronic control panel 2 motors for first rain collection systems with display
-
Motor’s data auto learning
-
Events and alarms data logger
-
Single-phase version with power relay for inductive loads (up to 31A)
-
Protection for motherboard
-
Remote control SALUPO CONNECT
Applications
Optional
GENERAL SPECIFICATIONS
- Operating voltage 230Vac +15/-20% 50/60Hz (SA692.xx)
- Operating voltage 400Vac +15/-20% 50/60Hz (SA695.xx)
- General disconnecting switch with door lock
- Button for automatic operation
- Button for manual operation (stable/unstable)
- Auxiliary circuit protection fuse
- Motors’ protection fuse
- N°2 contactors (SA695.xx)
- External thermoplastic box
- Cable glands
- Protection degree IP65
- Operating temperature -5/+50°C
- Relative humidity 60% at 50°C (not condensed)
ADVANTAGES
- Multilingual Display LCD to visualize:
- Operating voltage
- Current for each motor
- Hour counter for each motor
- Level status
- All information concerning the operation of the motors
- Minimum and maximum current auto learning for each motor
- Dry running with level control and minimum current
- Adjustable probes sensitivity
- Adjustable motor start waiting for decanting
- Deactivable alternance of the 2 motors
- 3s delay between the starting of the 2 motors
- Automatic switching in case of motor failure
- Adjustable supply mains waiting
- Operation with float switches and probes
INPUTS/OUTPUTS
- N°3 very low voltage inputs for float switches or probes (minimum/maximum1/maximum2)
- Very low voltage input for rain sensor
- N°2 very low voltage input for motor klixon
- Output 12Vdc max 200mA for rain sensor
- Alarm output 12Vdc max 200mA for Led flashing light
- Alarm output max 5A NC-COM-NO (pure contact)
PROTECTIONS
- Maximum and minimum current protection for each motor with alarm
- Lack and sequence of phases protection with automatic resent and alarm
- Minimum and maximum voltage protection with automatic reset and alarm
- Motor klixon protection for each motor with automatic reset and alarm
SINGLE-PHASE 230Vac +15/-20% 50/60Hz |
|||||||||
CODE | TYPE | POWER | OPERATING | DIMENSIONS mm | WEIGHT | BOX | |||
---|---|---|---|---|---|---|---|---|---|
kW | HP | CURRENT (A) | A-H | L-W | P-D | Kg | |||
SA692.00 | RAIN PLUS 2 230 | 0,37÷2,2 | 0,5÷3 | 2x(2÷18) | 285 | 245 | 140 | 2,4 | 03 |
THREE-PHASE 400Vac +15/-20% 50/60Hz |
|||||||||
CODE | TYPE | POWER | OPERATING | DIMENSIONS mm | WEIGHT | BOX | |||
---|---|---|---|---|---|---|---|---|---|
kW | HP | CURRENT (A) | A-H | L-W | P-D | Kg | |||
SA695.02L | RAIN PLUS 2 400 10 | 0,37÷7,5 | 0,5÷10 | 2x(0,5÷16) | 345 | 285 | 165 | 3,8 | 04 |
SA695.03L | RAIN PLUS 2 400 15 | 2,2÷11 | 3÷15 | 2x(4÷25) | 380 | 300 | 150 | 5,3 | 05 |
SA695.04L | RAIN PLUS 2 400 20 | 7,5÷15 | 10÷20 | 2x(16÷32) | 460 | 380 | 150 | 6,6 | 07 |
OPTIONALS |
|||||||||
CODE | TYPE | ||||||||
---|---|---|---|---|---|---|---|---|---|
OP100.29/B | On board GPRS expansion | ||||||||
OP100.39/B | On board Ethernet expansion | ||||||||
OP100.49/B | On board MODBUS RS-485 – BMS expansion | ||||||||
OP100.59/B | On board Ethernet – WiFi expansion | ||||||||
OP101.00 | Rain sensor with 2m cable and wall fixing bracket | ||||||||
OP100.05 | Wired single-phase surge arrester type 2 | ||||||||
OP100.05/1 | Wired three-phase surge arrester type 2 | ||||||||
OP200.00 | Alarm output 12Vdc 200mA and pure contact | ||||||||
OP100.13/1/12 | Wired siren 12Vdc | ||||||||
OP100.13/2/12L | Wired flashing Led lamp 12Vdc | ||||||||
SS100.00 | Visual and acoustic alarm indicator (BASIC ALARM VA012) | ||||||||
OP00.10 | Couple of brackets for collar (reference BOX 03-04) |
For more optionals click here
SPARE PARTS |
|||||||||
CODE | TYPE | ||||||||
---|---|---|---|---|---|---|---|---|---|
AC100.22/1/30 | Display electronic board with flat cable 20pin 30cm | ||||||||
SD692.20 | Single-phase RAIN PLUS 2 electronic board | ||||||||
SD695.20 | Three-phase RAIN PLUS 2 electronic board 20A | ||||||||
SD695.30-40 | Three-phase RAIN PLUS 2 electronic board 30-40A |