MULTIPLUS 2
Direct starting electronic control panel 2 motors for pressure booster, clean water and sewage with display
-
Multi application control panel
-
Motor’s data auto learning
-
Events and alarms data logger
-
Single-phase version with power relay for inductive loads (up to 31A)
-
Protection for motherboard
-
Remote control SALUPO CONNECT
Applications
Optional
GENERAL SPECIFICATIONS
- Operating voltage 230Vac +15/-20% 50/60Hz (SA694.xx)
- Operating voltage 400Vac +15/-20% 50/60Hz (SA697.xx)
- General disconnecting switch with door lock
- Button for automatic operation
- Button for manual operation (stable/unstable)
- Siren shut-off button
- Auxiliary circuit protection fuse
- Motors’ protection fuse
- N°2 contactors (SA697.xx)
- External thermoplastic box
- Cable glands
- Protection degree IP65
- Operating temperature -5/+50°C
- Relative humidity 60% at 50°C (not condensed)
ADVANTAGES
- Multilingual Display LCD to visualize:
- Operating voltage
- Current for each motor
- Hour counter for each motor
- Pressure switches status
- Level status
- System pressure with pressure transducer
- Tank level in meters with piezoresistive probe
- All information concerning the operation of the motors
- Minimum and maximum current auto learning for each motor
- Adjustable maximum number of startings per hour
- Adjustable motor starting test (24-48-72-96h)
- Dry running with level control and minimum current
- Adjustable probes sensitivity
- Deactivable alternance of the 2 motors
- 3s delay between the starting of the 2 motors
- Automatic switching in case of motor failure
- Loss of pressure control
- Adjustable mains supply returning
- Siren shut-off
- Operation with pressure switches, float switches, probes, pressure transducer and piezoresistive probe 4-20mA
INPUTS/OUTPUTS
- N°4 very low voltage inputs
- Input 4-20mA
- N°2 very low voltage inputs for motor klixon
- N°2 alarm outputs 12Vdc max 200mA for siren and flashing Led lamp
- Alarm output max 5A NC-COM-NO (pure contact)
PROTECTIONS
- Maximum and minimum current protection for each motor with alarm
- Lack and sequence of phases protection with automatic resent and alarm
- Minimum and maximum voltage protection with automatic reset and alarm
- Klixon protection for each motor with automatic reset and alarm
SINGLE-PHASE 230Vac +15/-20% 50/60Hz |
|||||||||
CODE | TYPE | POWER | OPERATING | DIMENSIONS mm | WEIGHT | BOX | |||
---|---|---|---|---|---|---|---|---|---|
kW | HP | CURRENT (A) | A-H | L-W | P-D | Kg | |||
SA694.00 | MULTIPLUS 2 230 | 0,37÷2,2 | 0,5÷3 | 2x(2÷18) | 285 | 245 | 140 | 2,4 | 03 |
THREE-PHASE 400Vac +15/-20% 50/60Hz |
|||||||||
CODE | TYPE | POWER | OPERATING | DIMENSIONS mm | WEIGHT | BOX | |||
---|---|---|---|---|---|---|---|---|---|
kW | HP | CURRENT (A) | A-H | L-W | P-D | Kg | |||
SA697.02L | MULTIPLUS 2 400 10 | 0,37÷7,5 | 0,5÷10 | 2x(0,5÷16) | 345 | 285 | 165 | 3,8 | 04 |
SA697.03L | MULTIPLUS 2 400 15 | 2,2÷11 | 3÷15 | 2x(4÷25) | 380 | 300 | 150 | 5,3 | 05 |
SA697.04L | MULTIPLUS 2 400 20 | 7,5÷15 | 10÷20 | 2x(16÷32) | 460 | 380 | 150 | 6,5 | 07 |
OPTIONALS |
|||||||||
CODE | TYPE | ||||||||
---|---|---|---|---|---|---|---|---|---|
OP100.29/B | On board GPRS expansion | ||||||||
OP100.39/B | On board Ethernet expansion | ||||||||
OP100.49/B | On board MODBUS RS-485 – BMS expansion | ||||||||
OP100.59/B | On board Ethernet – WiFi – expansion | ||||||||
OP100.99/B | On board expansion to detect water in the oil chamber up to 3 motors | ||||||||
OP100.01 | 3 level probes kit | ||||||||
OP100.05 | Wired single-phase surge arrester type 2 | ||||||||
OP100.05/1 | Wired three-phase surge arrester type 2 | ||||||||
OP100.13/1/12 | Wired siren 12Vdc | ||||||||
OP100.13/2/12L | Wired flashing Led lamp 12Vdc | ||||||||
SS100.00 | Visual and acoustic alarm indicator (BASIC ALARM VA012) | ||||||||
AC300.11.10-004.20 | Pressure transducer 0-10bar 4-20mA with 4m cable | ||||||||
AC300.11.16-004.20 | Pressure transducer 0-16bar 4-20mA with 4m cable | ||||||||
AC300.11.25-004.20 | Pressure transducer 0-25bar 4-20mA with 4m cable | ||||||||
AC300.20.01-005.00 | Piezoresistive probe 4-20mA with 5m cable | ||||||||
AC300.20.01-010.00 | Piezoresistive probe 4-20mA with 10m cable | ||||||||
AC300.20.02-010.20 | Piezoresistive probe 4-20mA with 10m cable for sewage | ||||||||
OP00.10 | Couple of brackets for collar (reference BOX 03-04) |
For more optionals click here
SPARE PARTS |
|
CODE | TYPE |
---|---|
AC100.22/1/30 | Display electronic board with flat cable 20pin 30cm |
SD694.20/1 | Single-phase MULTIPLUS 2 electronic board |
SD697.20/1 | Three-phase MULTIPLUS 2 electronic board 20A |
SD697.30-40/1 | Three-phase MULTIPLUS 2 electronic board 30-40A |