FROST CONTROL PLUS
Direct starting electronic control panel 1 motor for antifreeze function with display and temperature sensor
-
MOTOR’S DATA AUTO LEARNING
-
EVENTS AND ALARMS DATA LOGGER
-
REMOTE CONTROL SALUPO CONNECT
Applications
Optional
GENERAL SPECIFICATIONS
- Operating voltage 230Vac +15/-20% 50/60Hz (SA683.xx)
- Operating voltage 400Vac +15/-20% 50/60Hz (SA686.xx)
- General disconnecting switch with door lock
- Button for automatic operation
- Button for manual operation (stable/unstable)
- Antifreeze ON/OFF selector switch
- Temperature sensor -50/+100°C output 4-20mA
- Auxiliary circuit protection fuse
- Motor protection fuse
- Contactor (SA686.xx)
- External thermoplastic box
- Cable glands
- Protection degree IP65
- Operating temperature -5/+50°C
- Relative humidity 60% at 50°C (not condensed)
ADVANTAGES
- Multilingual Display LCD to visualize:
- Operating voltage
- Current
- Hour counter
- External temperature
- Level status
- All information concerning the operation of the motor
- Adjustable supply mains waiting
- Operation with pressure switch, float switches, probes and temperature sensor
- Dry running with 3 or 2 timed probes level control and minimum current
INPUTS / OUTPUTS
- Very low voltage input for level control (3 or 2 timed probes)
- N°2 very low voltage inputs for pressure switch, float switches or probes
- Input 4-20mA
- N°2 alarm outputs 12Vdc max 200mA for siren and flashing Led lamp
- Alarm output max 5A NC-COM-NO (pure contact)
PROTECTIONS
- Maximum and minimum current protection with alarm
- Lack and sequence of phases protection with automatic resent and alarm
- Minimum and maximum voltage protection with automatic reset and alarm
SINGLE-PHASE 230Vac +15/-20% 50/60Hz |
|||||||||
CODE | TYPE | POWER | OPERATING | DIMENSIONS mm | WEIGHT | BOX | |||
---|---|---|---|---|---|---|---|---|---|
kW | HP | CURRENT (A) | A-H | L-W | P-D | Kg | |||
SA683.00 | FROST CONTROL PLUS 230 | 0,37÷2,2 | 0,5÷3 | 2÷18 | 285 | 245 | 140 | 2,3 | 03 |
THREE-PHASE 400Vac +15/-20% 50/60Hz |
|||||||||
CODE | TYPE | POWER | OPERATING | DIMENSIONS mm | WEIGHT | BOX | |||
---|---|---|---|---|---|---|---|---|---|
kW | HP | CURRENT (A) | A-H | L-W | P-D | Kg | |||
SA686.02L | FROST CONTROL PLUS 400 10 | 0,37÷7,5 | 0,5÷10 | 0,5÷16 | 285 | 245 | 140 | 2,8 | 03 |
SA686.03L | FROST CONTROL PLUS 400 15 | 2,2÷11 | 3÷15 | 4÷25 | 345 | 285 | 165 | 3,4 | 04 |
SA686.04L | FROST CONTROL PLUS 400 20 | 7,5÷15 | 10÷20 | 16÷32 | 345 | 285 | 165 | 3,5 | 04 |
SA686.05L | FROST CONTROL PLUS 400 22 | 7,5÷16 | 10÷22 | 16÷36 | 380 | 300 | 150 | 4,9 | 05 |
SA686.06L | FROST CONTROL PLUS 400 25 | 7,5÷18,5 | 10÷25 | 16÷45 | 380 | 300 | 210 | 5,8 | 06 |
SA686.07L | FROST CONTROL PLUS 400 30 | 7,5÷22 | 10÷30 | 16÷52 | 460 | 380 | 210 | 7,1 | 08 |
OPTIONALS |
|||||||||
CODE | TYPE | ||||||||
---|---|---|---|---|---|---|---|---|---|
OP100.29/B | On board GPRS expansion | ||||||||
OP100.39/B | On board Ethernet expansion | ||||||||
OP100.59/B | On board Ethernet – WiFi – RS-485 expansion | ||||||||
OP100.05 | Wired single-phase surge arrester type 2 | ||||||||
OP100.05/1 | Wired three-phase surge arrester type 2 | ||||||||
OP200.00 | Alarm output 12Vdc 200mA and pure contact | ||||||||
OP100.13/1/12 | Wired siren 12Vdc | ||||||||
OP100.13/2/12L | Wired flashing Led lamp 12Vdc | ||||||||
SS100.00 | Visual and acoustic alarm indicator (BASIC ALARM VA012) | ||||||||
OP00.10 | Couple of brackets for collar (reference BOX 03-04) |
For more optionals click here
SPARE PARTS |
|||||||||
CODE | TYPE | ||||||||
---|---|---|---|---|---|---|---|---|---|
AC100.22/1/30 | Display electronic board with flat cable 20pin 30cm | ||||||||
SD683.20 | Single-phase FROST CONTROL PLUS electronic board | ||||||||
SD686.20 | Three-phase FROST CONTROL PLUS electronic board 20A | ||||||||
SD686.30-40 | Three-phase FROST CONTROL PLUS electronic board 30-40A | ||||||||
SD686.60 | Three-phase FROST CONTROL PLUS electronic board 60A |