STAR DELTA PLUS 2
Star delta starting electronic control panel 2 motors for pressure booster, clean water and sewage with display
-
Multi application control panel
-
Motor’s data auto learning
-
Events and alarms data logger
-
Protection for motherboard
-
Remote control SALUPO CONNECT
Applications
Optional
GENERAL SPECIFICATIONS
- Operating voltage 400Vac ±10% 50/60Hz
- General disconnecting switch with door lock
- Button for automatic operation
- Button for manual operation (stable/unstable)
- Siren shut-off button
- N°2 adjustable star delta timers
- Protection fuse for each motor
- Motor protection fuse
- N°6 contactors
- Connection terminal board
- External metal box
- Protection degree IP55
- Operating temperature -5/+40°C
ADVANTAGES
- Multilingual Display LCD to visualize:
- Operating voltage
- Current for each motor
- Hour counter for each motor
- Pressure switches status
- Level status
- System pressure with pressure transducer
- Tank level in meters with piezoresistive probe
- All information concerning the operation of the motors
- Minimum and maximum current auto learning for each motor
- Adjustable maximum number of startings per hour
- Adjustable motor starting test (24-48-72-96h)
- Dry running with level control and minimum current
- Adjustable probes sensitivity
- Deactivable alternance of the 2 motors
- 3s delay between the starting of the 2 motors
- Automatic switching in case of motor failure
- Loss of pressure control
- Adjustable mains supply returning
- Siren shut-off
- Operation with pressure switches, float switches, probes, pressure transducer and piezoresistive probe 4-20mA
INPUTS/OUTPUTS
- N°4 very low voltage inputs
- Input 4-20mA
- N°2 very low voltage inputs for motor klixon
- N°2 alarm outputs 12Vdc max 200mA for siren and flashing Led lamp
- Alarm output max 5A NC-COM-NO (pure contact)
PROTECTIONS
- Maximum and minimum current protection for each motor with alarm
- Lack and sequence of phases protection with automatic reset and alarm
- Minimum and maximum voltage protection with automatic reset and alarm
- Motor klixon protection for each motor with automatic reset and alarm
THREE-PHASE 400Vac ± 10% 50/60Hz |
|||||||||
CODE | TYPE | POWER | OPERATING | DIMENSIONS mm | WEIGHT | BOX | |||
---|---|---|---|---|---|---|---|---|---|
kW | HP | CURRENT (A) | A-H | L-W | P-D | Kg | |||
SQ697.00/SD | STAR DELTA PLUS 2 400 7,5 | 5,5 | 7,5 | 2x(10÷17) | 600 | 400 | 230 | 18 | 60 |
SQ697.01/SD | STAR DELTA PLUS 2 400 10 | 7,5 | 10 | 2x(13÷21) | 600 | 400 | 230 | 18 | 60 |
SQ697.02/SD | STAR DELTA PLUS 2 400 12,5 | 9,2 | 12,5 | 2x(19÷26) | 600 | 400 | 230 | 18 | 60 |
SQ697.03/SD | STAR DELTA PLUS 2 400 15 | 11 | 15 | 2x(22÷30) | 600 | 400 | 230 | 18 | 60 |
SQ697.04/SD | STAR DELTA PLUS 2 400 17,5 | 13 | 17,5 | 2x(25÷33) | 600 | 400 | 230 | 18 | 60 |
SQ697.05/SD | STAR DELTA PLUS 2 400 20 | 15 | 20 | 2x(32÷40) | 700 | 500 | 240 | 26 | 70 |
SQ697.06/SD | STAR DELTA PLUS 2 400 25 | 18,5 | 25 | 2x(38÷50) | 700 | 500 | 240 | 27 | 70 |
SQ697.07/SD | STAR DELTA PLUS 2 400 35 | 22÷26 | 30÷35 | 2x(45÷65) | 800 | 600 | 290 | 27 | 80 |
SQ697.08/SD | STAR DELTA PLUS 2 400 40 | 30 | 40 | 2x(60÷75) | 800 | 600 | 290 | 28 | 80 |
SQ697.09/SD | STAR DELTA PLUS 2 400 50 | 37 | 50 | 2x(65÷90) | 800 | 600 | 290 | 40 | 80 |
SQ697.10/SD | STAR DELTA PLUS 2 400 60 | 45 | 60 | 2x(70÷105) | 800 | 600 | 290 | 42 | 80 |
SQ697.11/SD | STAR DELTA PLUS 2 400 75 | 51,5÷55 | 70÷75 | 2x(75÷110) | 1000 | 800 | 370 | 65 | 103 |
SQ697.12/SD | STAR DELTA PLUS 2 400 80 | 60 | 80 | 2x(80÷150) | 1000 | 800 | 370 | 67 | 103 |
SQ697.13/SD | STAR DELTA PLUS 2 400 90 | 66 | 90 | 2x(80÷150) | 1200 | 800 | 370 | 68 | 122 |
SQ697.14/SD | STAR DELTA PLUS 2 400 100 | 75 | 100 | 2x(90÷180) | 1200 | 800 | 370 | 72 | 122 |
OPTIONALS |
|||||||||
CODE | TYPE | ||||||||
---|---|---|---|---|---|---|---|---|---|
OP100.29/B | On board GPRS expansion | ||||||||
OP100.39/B | On board Ethernet expansion | ||||||||
OP100.49/B | On board MODBUS RS-485 expansion | ||||||||
OP100.59/B | On board Ethernet – WiFi – expansion | ||||||||
OP100.99/B | On board expansion to detect water in the oil chamber up to 3 motors | ||||||||
OP100.01 | 3 level probes kit | ||||||||
OP100.05/1 | Wired three-phase surge arrester type 2 | ||||||||
SS100.00 | Visual and acoustic alarm indicator (BASIC ALARM VA012) | ||||||||
AC300.11.10-004.20 | Pressure transducer 0-10bar 4-20mA with 4m cable | ||||||||
AC300.11.16-004.20 | Pressure transducer 0-16bar 4-20mA with 4m cable | ||||||||
AC300.11.25-004.20 | Pressure transducer 0-25bar 4-20mA with 4m cable | ||||||||
AC300.20.01-005.00 | Piezoresistive probe 4-20mA with 5m cable | ||||||||
AC300.20.01-010.00 | Piezoresistive probe 4-20mA with 10m cable | ||||||||
AC300.20.02-010.20 | Piezoresistive probe 4-20mA with 10m cable for sewage |
For more optionals click here
SPARE PARTS |
|||||||||
CODE | TYPE | ||||||||
---|---|---|---|---|---|---|---|---|---|
AC100.22/1/50 | Display electronic board with flat cable 20pin 50cm | ||||||||
AC100.22/1/80 | Display electronic board with flat cable 20pin 80cm | ||||||||
AC100.22/1/100 | Display electronic board with flat cable 20pin 100cm | ||||||||
SD697.20/1 | Three-phase MULTIPLUS 2 electronic board 20A | ||||||||
SD697.30-40/1 | Three-phase MULTIPLUS 2 electronic board 30-40A | ||||||||
SD697.60/1 | Three-phase MULTIPLUS 2 electronic board 60A | ||||||||
SD697.100/1 | Three-phase MULTIPLUS 2 electronic board 100A | ||||||||
SD697.200/1 | Three-phase MULTIPLUS 2 electronic board 200A |