THREE MOTORS PLUS
Direct starting electronic control panel 3 motors for pressure booster with display
-
Multi application control panel
-
Motor’s data auto learning
-
Events and alarms data logger
-
Protection for motherboard
-
Remote control SALUPO CONNECT
Applications
Optional
GENERAL SPECIFICATIONS
- Operating voltage 400Vac +15/-20% 50/60Hz
- General disconnecting switch with door lock
- Button for automatic operation
- Button for manual operation (stable/unstable)
- Auxiliary circuit protection fuse
- Motors’ protection fuse
- N°3 contactors
- External thermoplastic box
- Cable glands
- Protection degree IP65
- Operating temperature -5/+40°C
ADVANTAGES
- Multilingual Display LCD to visualize:
- Operating voltage
- Current for each motor
- Hour counter for each motor
- Pressure switches status
- Level status
- System pressure with pressure transducer
- All information concerning the operation of the motors
- Minimum and maximum current auto learning for each motor
- Dry running with level control and minimum current
- Deactivable alternarce of the 3 motors
- 3s delay between the starting of the 3 motors
- Automating switching in case of motor failure
- Loss of pressure control
- Adjustable mains supply returning
- Operation with pressure switches, float switches, probes and pressure transducer
INPUTS / OUTPUTS
- Very low voltage input for start 1 pressure switch
- Very low voltage input for start 2 pressure switch
- Very low voltage input for emergency pressure switch
- Input 4-20mA
- N°2 very low voltage inputs for float switches or probes
PROTECTIONS
- Maximum and minimum current protection for each motor with alarm
- Lack and sequence of phases protection with automatic resent and alarm
- Minimum and maximum voltage protection with automatic reset and alarm
THREE-PHASE 400Vac +15/-20% 50/60Hz |
|||||||||
CODE | TYPE | POWER | OPERATING | DIMENSIONS mm | WEIGHT | BOX | |||
---|---|---|---|---|---|---|---|---|---|
kW | HP | CURRENT (A) | A-H | L-W | P-D | Kg | |||
SA656.02L | THREE MOTORS PLUS 400 10 | 0,37÷7,5 | 0,5÷10 | 3x(0,5÷16) | 380 | 300 | 150 | 6,4 | 05 |
SA656.03L | THREE MOTORS PLUS 400 15 | 2,2÷11 | 3÷15 | 3x(4÷25) | 460 | 380 | 150 | 7,4 | 07 |
SA656.04L | THREE MOTORS PLUS 400 20 | 7,5÷15 | 10÷20 | 3x(16÷32) | 460 | 380 | 150 | 7,5 | 07 |
OPTIONALS |
|
CODE | TYPE |
---|---|
OP100.29/B | On board GPRS expansion |
OP100.39/B | On board Ethernet expansion |
OP100.49/B | On board MODBUS RS-485 – BMS expansion |
OP100.59/B | On board Ethernet – WiFi – RS-485 expansion |
OP100.01 | 3 level probes kit |
OP100.05/1 | Wired three-phase surge arrester type 2 |
OP200.00 | Alarm output 12Vdc 200mA and pure contact |
OP100.13/1/12 | Wired siren 12Vdc |
OP100.13/2/12L | Wired flashing Led lamp 12Vdc |
SS100.00 | Visual and acoustic alarm indicator (BASIC ALARM VA012) |
AC300.11.10-004.20 | Pressure transducer 0-10bar 4-20mA with 4m cable |
AC300.11.16-004.20 | Pressure transducer 0-16bar 4-20mA with 4m cable |
AC300.11.25-004.20 | Pressure transducer 0-25bar 4-20mA with 4m cable |
For more optionals click here
SPARE PARTS |
|
CODE | TYPE |
---|---|
AC100.22/1/30 | Display electronic board with flat cable 20pin 30cm |
SD656.20/1 | Three-phase PRESS CONTROL PLUS electronic board 20A |
SD656.30-40/1 | Three-phase PRESS CONTROL PLUS electronic board 30-40A |